2-12 Extreme Networks Consolidated Hardware Guide
Site Preparation
Rack Specifications and Recommendations
Racks should conform to conventional standards. In the United States, refer to EIA
Standard RS-310C: Racks, Panels, and Associated Equipment. In countries other than
the United States, refer to IEC Standard 297. In addition, verify that your rack meets the
basic mechanical and space requirements that are described in this section.
Mechanical Recommendations for the Rack
Use distribution racks that meet the following mechanical recommendations:
Use an open style, 19-inch (48.26-cm) rack to facilitate easy maintenance and to
provide proper ventilation.
The rack should use the universal mounting rail hole pattern that is identified in IEC
Standard 297.
The mounting holes should be flush with the rails to accommodate the chassis.
Use a rack made of steel or aluminum.
Install equipment into the lower half of the rack first to avoid making the rack
top-heavy.
The rack should support approximately 600 pounds (272 kilograms).
Protective Grounding for the Rack
Use a rack grounding kit and a ground conductor that is carried back to earth or to
another suitable building ground.
All Extreme Networks switches are designed with mounting brackets that provide solid
metal-to-metal connection to the rack. If you do not use equipment racks, you can
attach wiring terminals directly to the mounting brackets for appropriate grounding.
Alpine products have grounding terminals that are mounted on the back of the chassis.
At minimum, follow these guidelines:
Ground equipment racks to earth ground.
CAD weld appropriate wire terminals to building I-beams or earth ground rods.
Use #4 copper wire.
Drill and tap wire terminals to equipment racks.